Generally, the TSC2 series fuse cutout contains load type and common type in light of structure difference. It can be divided into 12kV, 24kVand 36kV types based on applicable rated voltage.

Technical Parameters of the Fuse Cutout
ModelTSC2-12 TSC2-20TSC2-36
Rated voltage12kV 24kV 36kV
Rated frequency 50Hz
Rated current100A, 200A, 300A (isolating switch blade)100A 100A
Power frequency withstand voltage (phase to phase/between interrupting points)50kV/60kV70kV/80kV100kV/110kV
Lightning impulse withstand voltage (phase to phase/between interrupting points)110kV/125kV150kV/165kV195kV/210kV
Rated switching off current12.5KA, 16KA (each fuse tube enables short circuit switching off for two times.) 12.5KA 10KA
Mechanical life2000 times
Creepage distance≤31mm/kV (Large creepage distance is also available.)
Cut-off load current100A/200A
Weight 6.5kg 12kg 16kg

Components of the Fuse Cutout

    1. This fused cut out can be fitted with cast copper parallel-groove connector. (optional configuration)
    2. Stainless steel protective cover
    3. We equip the silver-to-silver top contact of our fuse cutout with stainless steel compression spring.
    4. Brass pull ring
    5. To prevent fuse tube from switch-off shaking, a high-strength silver coated cast copper lug is used.
    6. The stainless steel spring plate of this fuse cut out facilitates prompt fuse wire drawing.
    7. Dual current diversion is achieved thanks to silver-to-silver lower contact.
    8. High-strength bird-proof insulator
    9. Stainless steel mounting bracket
    10. Arc-extinguishing chamber (optional configuration)
    11. Auxiliary conducting loop
    12. Our fuse cutout is available with anti-UV epoxy tube. (optional configuration)