Oil Immersed Power Transformer

Oil Immersed Power Transformer
Oil Immersed Power Transformer
Oil Immersed Power Transformer
Oil Immersed Power Transformer
Oil Immersed Power Transformer
Oil Immersed Power Transformer
Request a Quote

Brief Description
The oil immersed distribution transformer is completely sealed against outside air and moisture to keep transformer oil clean and free from contamination. Flexible corrugated oil tank design (for cooling and heat dissipation) accommodates the change of transformer volume. Insulation material such as high-voltage bushings offers a long service life. There is no need to check up the core yoke before getting the transformer started. No maintenance or repair is required as the distribution transformer will last for years to come. This product is also designed with conservator protection.

Known for outstanding performance and significant energy savings. When equipped with an on-load tap changer, this transformer allows remote voltage control manually or automatically. Extended voltage adjustment range: ±3×3%. Handles large loads with minimum temperature increase in the coil. Rigid construction features a conservator acting as a reservoir for transformer oil. Widely used in hydroelectric power stations as well as power grids requiring constant voltage or involving frequent, dramatic voltage changes.

Applications
Ideal for any power distribution sites as well as European style compact substations and mobile substations

Standards
IEC60076
GB10094

Product Specifications
  • Corrugated tank with fins for heat dissipation

  • On-load tap changer changes the tap position, which then alters the number of winding turns connected to one circuit thereby adjusting voltage without powering off the circuit.

  • Pressure relief valve ensures safety all while keeping air and moisture out of the transformer oil.

  • Oil injection port is where oil temperature can be measure.

Outline & Dimensions
Technical Specs
S11-30~2500/10 Series Distribution Transformer with Conservator Parameters
Model No. Rated Voltage Vector Group No-Load loss at75 °C Load loss at 75 °C No-load Current% Impedance Voltage % Weight(kg) Distance between Yokes Dimensions (mm)
H.V(kV) % L.V.(kV) (W) (W) Body Oil G.W. (E1=E2) LxWxH
S11-30 6 6.3 10 10.5 11 ( 1x2.5) 0 (-3 x 2.5)% 0.4 100 630/600 0.4 4 195 80 335 400 800x620x1000
S11-50 130 910/870 0.4 280 100 460 400 840x650x1100
S11-63 150 1090/1040 0.4 310 115 500 400 870x670x1120
S11-80 180 1310/1250 0.35 335 125 560 400 900x700x1190
S11-100 200 1580/1500 0.35 420 130 650 400 920x720x1210
S11-125 240 1890/1800 0.30 450 150 740 550 940x740x1230
S11-160 280 2310/2200 0.30 540 170 900 550 960x800x1270
S11-200 298 2666/2294 0.30 630 190 950 550 1050x770x1320
S11-250 400 3180/3050 0.25 820 210 1160 550 1080x800x1300
S11-315 Dyn11 480 3830/3650 0.25 900 230 1400 550 1080x800x1400
S11-400 Yyn0 570 4520/4300 0.25 1040 270 1630 550 1220x830x1460
S11-500 680 5410/5150 0.25 1230 280 1730 660 1350x830x1500
S11-630 810 6200 0.23 4.5 1420 350 2050 660 1370x940x1550
S11-800 980 7500 0.23 1600 400 2570 820 1650x980x1580
S11-1000 1150 10300 0.20 1820 480 2950 820 1780x1160x1700
S11-1250 1360 12000 0.20 2480 560 3700 820 1800x1180x1730
S11-1600 1640 14500 0.20 3100 640 4550 820 1930x1260x1860
S11-2000 2020 18270 0.18 3450 800 5350 1070 1980x1300x2050
S11-2500 2380 21210 0.18 4050 900 6080 1070 2000x1300x2180
Note: Above data are for reference only.