Hook-Up Wire, UL1015

Hook-Up Wire, UL1015
Request a Quote

About UL1015
Manufacture standard: UL758
Rated voltage: 600 Vac or 750 Vdc
Temperature range: -40 to 80℃, -40 to 90℃,-40 to 105 ℃
Voltage of spark testing: 6kV/AC
Conductor: Tinned copper
Insulator: PVC
Flame retardant performance: Passing UL VW-1 and CSA FT1 vertical flame tests
Environmental protection: ROHS standard
Color: Black, brown, red, orange, yellow, green, blue, purple, gray and white.
Application: Internal wiring and electronic equipment

Technical Parameters of UL Hook up Wire
Conductor Insulator Conductor resistance (Tinned copper) Standard length
Wire gauge Structure Diameter Nominal thickness Min. thickness Nominal external diameter Max. value (20℃) English unit Metric unit
AWG Number of wires/Wire diameter (mm) mm mm mm mm Ω /km FT m
30 1/0.254 0.254 0.76 0.69 1.80±0.1 361 2000 610
7/0.10 0.30 0.76 0.69 1.90±0.1 381
28 1/0.32 0.32 0.76 0.69 1.90±0.1 227
7/0.127 0.38 0.76 0.69 2.0±0.1 239
26 1/0.404 0.404 0.76 0.69 2.0±0.1 143
7/0.16 0.48 0.76 0.69 2.1±0.1 150
24 11/0.16 0.61 0.76 0.69 2.2±0.1 94.2
22 17/0.16 0.76 0.76 0.69 2.4±0.1 59.4
20 26/0.16 0.94 0.76 0.69 2.6±0.1 37.4
18 41/0.16 1.18 0.76 0.69 2.8±0.1 23.5
16 26/0.254 1.50 0.76 0.69 3.1 ± 0.15 14.6 1000 305
14 41/0.254 1.18 0.76 0.69 3.4 ± 0.15 9.15
12 65/0.254 2.36 0.76 0.69 4.0 ± 0.15 5.75
10 105/0.254 3.40 0.76 0.69 5.0 ± 0.15 3.55
8 119/0.30 4.30 1.14 1.02 6.7 ± 0.15 2.27
6 189/0.30 5.40 1.52 1.37 8.6 ± 0.20 1.41 500 152.5
4 299/0.30 6.80 1.52 1.37 10.0 ± 0.20 0.882
2 476/0.30 8.70 1.52 1.37 11.9 ± 0.20 0.566
Notes: 1. We can manufacture the hook-up wire according to client's drawing or sample.
2. The structure of conductor is either solid or stranded. For example, "7/0.10" means the conductor is stranded by 7 wires and the wire has a diameter of 0.10mm.
Related products
Send Message
Other Products
Inquiry
Inquiry