Temperature Transmitter
Request a Quote
Our temperature transmitter employs thermocouple, RTD, etc. as the temperature sensor. The sensor serves to output signal to the transmitter module. Through processes such as voltage stabilization, smoothing, operational amplification, non-linearity correction, voltage to current conversion, constant current and reverse polarity protection, the signal from the sensor is converted into 4~20mA electrical current signal which has linear relationship with the temperature.
Temperature transmitters are widely used for industrial temperature measurement and process control purposes in fields such as textile, rubber, metallurgy, pharmaceutical, and food processing.
Technical SpecificationsType | Temperature range ( ℃ ) | Min. measuring range ( ℃ ) | Absolute error | Intrinsic error |
K | 0~1300 | 120 | ±1 ℃ | ±0.2% |
E | 0~1000 | 80 | ±1 ℃ | ±0.2% |
S | 0~1600 | 580 | ±3 ℃ | ±0.2% |
B | 400~1800 | 1000 | ±3 ℃ | ±0.2% |
R | 0~1600 | 850 | ±3 ℃ | ±0.2% |
T | -200~400 | 120 | ±1 ℃ | ±0.2% |
N | 0~1200 | 180 | ±3 ℃ | ±0.2% |
W | 0~2300 | 340 | ±3 ℃ | ±0.2% |
J | 0~1200 | 100 | ±3 ℃ | ±0.2% |
Input
Thermocouple type | K, E, S, B, T, J, etc. |
Measuring range ( ℃ ) | 0-1300, 0-1000, 0-1600, 400-1800, -200 to 400, 0-1200 |
Input resistance | ≥20KΩ |
Cold junction compensation | -15 ~ 75 ℃ |
Output current | 4 ~ 20mA |
Output circuit power supply | 12 ~ 30VDC |
Min. working voltage | 12VDC |
Standard accuracy | ±0.2% |
Temperature drift | Intrinsic error /10 ℃ |
Lead-wire compensation of thermocouple | ±0.1% (0 ~ 10Ω) |
Error caused by load change | ±0.1% (within allowable load) |
Error caused by power supply fluctuation | ±0.1% (12 ~ 30V) |
Starting up response time | <1S (0 ~ 90%) |
Operating temperature | -20 ~ 70 ℃ |
Protection grade | IP00/IP54 (determined by protection grade of sensor) |
Electromagnetic compatibility | IEC61000, EN61000 |
Input
Measuring range | Pt100 RTD: -200~850 ℃ Cu50 RTD: -50~150 ℃ |
Min. temperature range | 50 ℃ |
Lead resistance | ≤10Ω |
Output current | 4 ~ 20mA |
Output circuit power supply | 12 ~ 30VDC |
Min. working voltage | 12VDC |
Relationship between load resistance and power supply voltage | Load resistance (including lead resistance) = power supply voltage (V) - 12 (V) /0.02A |
Standard accuracy | ±0.2% (custom accuracy is available) |
Temperature drift | Intrinsic error /10 ℃ |
Lead-wire compensation of RTD | ±0.1% (0 ~ 10Ω) |
Error caused by load change | ±0.1% (within allowable load ) |
Error caused by power supply fluctuation | ±0.1% (12 ~ 30V) |
Starting up response time | <1S (0 ~ 90%) |
Operating temperature | -20 ~ 70 ℃ |
Protection grade | IP00/IP54 (determined by protection grade of sensor) |
Electromagnetic compatibility | IEC61000, EN61000 |