0.6/1kV PVC Insulated Power Cable

0.6/1kV PVC Insulated Power Cable
0.6/1kV PVC Insulated Power Cable
0.6/1kV PVC Insulated Power Cable
0.6/1kV PVC Insulated Power Cable
Request a Quote

Welcome to Leshan, a specialist Chinese power cable provider. This page is dedicated to the PVC insulated power cable. The 6/1kV PVC insulated power cable is used to transmit and distribute electricity on AC rated voltage 0.6/1kV power lines U0/U.

Standards compliance for PVC insulated power cable
GB/T12706.1-2008 (Reference standard: IEC60502-1) Rated Voltage 1kV (Um=1.2kV)

Working conditions for PVC insulated power cable
1. Maximum working temperature: 70℃
2. In case of a short (lasting less than 5 seconds) maximum temperature of the cable conductor will not exceed 160℃
3. Environment temperature should be no lower than 0℃ when laying the cable
4. Bending radius allowance of the insulated cable: Single core cable: Unarmored cable 20D; Steel tape armored cable 15D; Triple core cable: Unarmored cable 15D; Steel tape armored cable 12D
Notes: D= practical external diameter of cable.

Rated cross area(mm2) 0.5 0.75 1 1.5 2.5 4 6 10
Cu Non tinned 36 24.5 18.1 12.1 7.41 4.61 3.08 1.83
(Ω/km) Tinned 36.7 24.8 18.2 12.2 7.56 4.7 3.11 1.84
Al(Ω/km) / / / 18.1 12.1 7.41 4.61 3.08
Rated cross area(mm2) 16 25 35 50 70 95 120 150
Cu Non tinned 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124
(Ω/km) Tinned 1.16 0.734 0.529 0.391 0.27 0.195 0.154 0.126
Al(Ω/km) 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206
Rated cross area(mm2) 185 240 300 400 500 630 800 1000
Cu Non tinned 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
(Ω/km) Tinned 0.1 0.0762 0.0607 0.0475 0.0369 0.0286 0.0224 0.0177
Al(Ω/km) 0.164 0.125 0.1 0.0778 0.0605 0.0469 0.0367 0.0291
Type Description Application Occasion
Cu Al
VV VLV PVC insulation PVC sheath power cable These cables can be laid indoors, in tunnels, cable furrows or pipes. It cannot bear an outside mechanical force.
VV22 VLV22 PVC insulation, steel tape armor, PVC sheath power cable These cables are applicable for use underground, and can bear a limited mechanical force.
VV62 VV62 PVC insulation, has none of the magnetism steel tape armor does, PVC sheath power cable.
VV32 VLV32 PVC insulation, thin steel-wire armor, PVC sheath power cable These cables are applicable for wells or underwater in bodies of water. They can bear a larger pressure with a lead to pull the force.
VV72 VLV72 PVC insulation, has none of the magnetism thick steel-wire armor does, PVC sheath power cable
VV42 VLV42 PVC insulation, thick steel-wire armor, PVC sheath power cable
Hint specially The single-core magnetism material that packs the cable is not applicable for use with AC power supply packs. The necessary hour limit uses a single-core 62 or 72 type power pack for the cable. In order to prevent a decrease in the cable’s electric current transport ability, it does not allow the (cent) [GF1] to cross the magnetism piping when used with a single core cable.
Cross No 1 2 3 3 1 4 3 2 4 1 5
Area 4~500 2.5~500 2.5~300 4~300 2.5~300 2.5~300 4~300 2.5~95
Related products
Send Message
Other Products
Inquiry
Inquiry