1kV / 10kV Aerial Insulated Cable

1kV / 10kV Aerial Insulated Cable
1kV / 10kV Aerial Insulated Cable
1kV / 10kV Aerial Insulated Cable
Request a Quote

Leshan boasts a fruitful history of serving various cable installation projects constructed around the world. This page details the overhead cable.

The 1kV and 10 kV aerial insulated cables consist of a copper or aluminum conductor, an inner shielding layer, weather-proof insulation material, and an outer shielding layer. This type of power wire is favored for use in suspended power line systems, such as on utility poles and electrical pylons, which is advantageous because the cost is much lower compared to underground lines.

Standards Compliance of Aerial Insulated Electrical Wire
GB/T12527-2008 1kV Aerial insulation cable. (According to IEC502, IEC227 Standard)
GB/T14049-2008 10kV Aerial insulation cable

Working conditions of aerial insulated cable
1. Rated voltage: 1kV, 10kV.

2. Maximum working temperature:
XLPE insulation cable: 90℃
HDPE insulation cable: 75℃

3. In case of a short(lasting less than 5 seconds), maximum temperature:
XLPE insulated cables: 250℃
HDPE insulated cables: 150℃

4. During cable laying, the ambient temperature must be above -20℃.

5. Bending radius allowance of the cable
1kV insulated air cable
no less than 4D for the cable with outer diameter less than 25mm
no less than 6D for the cable with outer diameter of 25mm or more.
10kV aerial insulation power cable:
Single core cable: 20 (D d)±5%mm.
Multi-core cable: 15 (D d)±5%mm
D = Actual cable outer diameter.
d = Actual conductor outer diameter.

Type Name Application
JKTRYJ Soft copper conductor XLPE insulation aerial cable The transformer connects to the line.
JK(L)YJ Cu (Al) conductor XLPE insulation Aerial cable When permanently laying the cable, users must keep a certain distance between the cable and trees. During power transmission, the cable can be connected to the trees for a variety of purposes.
JK(L)Y Cu (Al) conductor XLPE insulation Aerial cable
JKLGYJ Steel-Al conductor XLPE insulation Aerial cable
JKLGY Steel-Al conductor HDPE insulation Aerial cable
JKLYJ/Q Al conductor light XLPE insulation Aerial cable When permanently laying the cable, users must keep a certain distance between the cable and the trees. During power transmission, the cable can come into short amounts of contact with the trees.
JKLY/Q Al conductor light HDPE insulation Aerial cable
JKLGYJ/Q Steel-Al conductor light XLPE insulation Aerial cable
JKLGY/Q Steel-Al conductor light HDPE insulation Aerial cable
Type Core Number Nominal cross-section area (mm2)
1kV 10kV
JK(L)YJ JK(L)Y
JKTRYJ JKTRY
1 16~240 25~300
3 10~120 25~300
4 10~120 ---
JK(L)YJ/Q JK(L)Y/Q 1 --- 25~300
JKLGYJ JKLGY 1 25/4~300/40 25/4~300/40
JKLGYJ/Q 1 --- 25/4~300/40
NCS-Area (mm2) Maximum Conductor Resistance at 20°C, Ω/km Insulate resistance MΩ.km Conductor Min Splitting Source(N)
1kV 10kV
Hard Cu Cu Al 70℃ 90℃ 20℃ Hard Cu Al
10 1.906 1.83 3.08 0.0067 0.67 Common 1500 Light 1000 3471 1650
16 1.198 1.15 1.91 0.0065 0.65 5486 2517
25 0.749 0.727 1.20 0.0054 0.54 8465 3762
35 0.540 0.524 0.868 0.0054 0.54 11731 5177
50 0.399 0.387 0.641 0.0046 0.46 16502 7011
70 0.276 0.268 0.443 0.0040 0.40 23461 10354
95 0.199 0.193 0.320 0.0039 0.39 31759 13727
120 0.158 0.153 0.253 0.0035 0.35 39911 17339
150 0.128 / 0.206 0.0035 0.35 49505 21033
185 0.1021 / 0.164 0.0035 0.35 61846 26732
240 0.0777 / 0.1250 0.0034 0.34 79823 34679
300 0.0619 / 0.100 / / 99788 43349
Rrated voltage Test voltages Test duration
1kV 3.5kV 1min
10 kV Common Insulation Type 18kV 1min
Light Insulation Type 12kV
Nominal Area (mm2) Reference diameter (mm) Approximate weight (kg/km)
JKYJ JKLYJ JKY JKLY
16 8.0 178 80 178 80
25 9.5 266 112 266 112
35 11.0 366 150 367 151
50 12.5 510 200 511 201
70 14.0 697 264 699 265
95 16.5 945 358 947 359
120 18.0 1175 435 1176 437
150 20.0 1470 512 1472 514
185 22.5 1813 590 1815 592
240 25.5 2343 668 2345 670
Al Nominal Area (mm2) Ste Nominal Area (mm2) Reference diameter (mm) Approximate weight (kg/km)
JKLGYJ JKLGY
25 4 9.2 134 134
35 6 10.8 180 180
50 8 12.0 241 241
70 10 13.8 318 318
95 15 16.2 442 443
120 20 17.8 556 557
150 25 19.8 695 696
185 30 22.4 892 894
240 30 25.0 1147 1149
300 40 28.6 1424 1426
Al Nominal Area Reference diameter (mm) Approximate weight (kg/km)
JKYJ JKLYJ JKY JKLY
25 15 348 194 349 195
35 16 450 234 451 235
50 18 600 290 601 291
70 19 800 366 801 367
95 21 1050 462 1052 464
120 23 1290 548 1292 550
150 24. 1580 650 1582 652
185 26 1910 766 1912 768
240 28 2430 943 2432 945
300 30 2991 1134 2994 1137
Al Nominal Area(mm2) Reference diameter (mm2) Approximate weight (kg/km)
JKYJ/Q JKLYJ/Q JKY/Q JKLY/Q
25 13.0 312 157 313 158
35 14.0 411 194 412 195
50 15.3 557 247 559 249
70 17.0 760 326 761 327
95 18.8 1008 419 1010 421
120 20.2 1246 502 1248 504
150 21.8 1530 600 1532 604
185 23.4 1859 712 1861 7156
240 25.6 2373 885 2375 889
300 27.8 2929 1069 2932 1072
Al Nominal Area (mm2) Ste Nominal Area (mm2) Reference diameter (mm) Approximate weight (kg/km)
JKLGYJ JKLGY
35 6 15.8 265 267
50 8 17.0 333 335
70 10 18.8 421 423
95 15 21.0 550 552
120 20 22.6 672 674
150 25 24.2 808 810
185 30 26.4 1003 1005
240 30 28.6 1251 1254
300 40 31.8 1524 1527
Al Nominal Area (mm2) Ste Nominal Area (mm2) Reference diameter (mm) Approximate weight (kg/km)
JKLGYJ/Q JKLGY/Q
25 4 12.0 171 172
35 6 13.0 218 219
50 8 14.2 283 284
70 10 16.0 366 367
95 15 18.0 487 489
120 20 19.6 606 607
150 25 21.2 737 739
185 30 23.4 926 928
240 30 25.6 1169 1171
300 40 28.8 1433 1435